arrow-left

Only this pageAll pages
gitbookPowered by GitBook
1 of 10

CMM 3CH

CMM-3CH

Loading...

Loading...

Loading...

Loading...

Loading...

Loading...

General

Loading...

Loading...

GUI Manual

hashtag
Introduction

The CMM-xCH modules are equipped with an Ethernet-CAN-Gateway and independent microcontrollers for each measurement channel. CAN-FD is used to communicate between the gateway and the channels.

The CMM-xCH modules can be connected via Ethernet or with a direct connection to the internal CAN Bus.

For CAN-FD communication a DBC file is available on request. For communication via Ethernet the tool "IRS.CMM-xCH" can be used. It can be downloaded from https://docs.irs.systems/. Alternatively the "IRS.CMM-xCH.Shared.dll" can be used to integrate the CMM-xCH modules into your Software.

hashtag
Using the IRS.CMM-xCH GUI

hashtag
Connecting the module

To connect to the module, enter the IP address of the module and click connect. If you do not know the IP address of the module you can use "Tools -> DiscoveryTool" to detect connected modules.

The FDCAN settings are used for the internal communication and normally the default setting can be used. If the settings were changed before, the "EDIT" button can be used to select the changed settings. If the settings are unknown the "DETECT CAN BAUDRATE" button can be used.

hashtag
Changing the IP address

To change the IP address of the module, use "Tools -> DiscoveryTool". In the DicoveryTool first click "START DISCOVER". After 10 seconds a list of all connected modules is shown. Select the module you want to change and click "ETHERNET CONFIG". In the following window you can enter the new IP address and click "UPDATE". You need to power cycle the module to apply the new IP address.

As an alternative you can configure the IP address in a limited range with the DIP switch on the PCB. The switches are treated as a binary number and marked with their place value (1, 2, 4). Depending on the set binary number an IP address between 192.168.222.1 and 192.168.222.7 is used. If all three switches are "off" the IP address configured with the DiscoveryTool is used. The switches are read at power up. So after changing the switches a power cycle is required.

hashtag
Updating the firmware

hashtag
Ethernet-CAN-Gateway

To update the Ethernet-CAN-Gateway firmware, use "Tools -> Bootloader Gateway". This opens the following window:

Enter the IP address and click on "START". Select the firmware image in the file selection dialog. The firmware image is include in the folder "firmware" of the GUI installation folder and named "STM32H7-Gateway.tinyimg2".

hashtag
Measurement channels

To update the firmware of the measurement channels, use "Tools -> Bootloader CMM". This opens the following window:

You only need to enter the IP address of the module and then click "START". The rest of the settings should be preset to the correct values. If the settings were changed, you can reload the default values by clicking "Presets -> CMM-xCH".

After clicking on "START", select the firmware image in the file selection dialog. The firmware image is include in the folder "firmware" of the GUI installation folder and named "STM32G4-Channel.tinyimg1".

hashtag
Configure board and channel

Multiple CMM-xCH boards can be connected via CAN bus. To address the individual boards, each board needs to be configured with a unique Board ID.

The configuration of the Board ID is done with the DIP switch on the board marked with "CAN ID". The switches are treated as a binary number and marked with their place value (1, 2, 4, ...). The switches are read at power up. So after changing the Board ID a power cycle is required.

When the Board IDs are set correctly, you can use the Ethernet-CAN-Gateway of any board to communicate with all connected boards. In the GUI click the dropdown menu under "BOARD/CHANNEL to see a list of all detected channels and to select the channel which shall be used. The channel IDs are fixed to 0 and 1 and can not be changed. The channels are marked on the PCB with "Channel 0" and "Channel 1".

hashtag
Configuring internal CAN bus

CAN baudrates and the uses of bitrate switching can be configured under "CAN CONFIGURATION".

CAN configuration can only be set for all connected channels not for individual channels. Otherwise communication between the channels could get broken, if different baudrates are set.

If the CAN configuration of connected boards is messed up and a configuration with the GUI is not possible you can use the jumper marked with "CAN Default" to reset the CAN configuration of the boards. The CMM-2CH needs to be power-cycled while the jumper is connected to reset the CAN configuration to its default value.

hashtag
Configuring measurement behavior

The channels of the CMM-xCH can send a cyclic CAN message with the measured values. Under "CHANNEL CONFIGURATION" the interval of these cyclic CAN messages can be adjusted. If the interval is set to zero, no cyclic CAN message are sent.

Furthermore the default state after power up of each measurement channel can be configured. If the default state is "off" the button "CMM ON" can be used to switch the measurement channel on.

The CMM-xCH modules automatically switch between ranges without interrupting then current flow in the measurement path. If however this switching is not desired, a minimum range can be set. The minimum range is reset to zero when rebooting the CMM-xCH.

A maximum range can not be set because it could easily lead to accidentally exceeding the maximum allowed current of the selected range.

hashtag
Reading measured values

To read the measured values, the button "MIN/AVG/MAX" und "MEASUREMENT" can be used. A pop up window opens, which shows the measured values since the last use of the button.

For continuous monitoring of the measured values the cyclic messages can be used. To use the cyclic messages a interval different from zero must be set under "CHANNEL CONFIGURATION". The cyclic message can be read by clicking the button "UPDATE" or by enabling the checkbox "auto update".

If auto update is enabled the chart on the right shows the current of the channel selected under "BOARD/CHANNEL".

hashtag
Using legacy IsoTP communication

The CMM-xCH supports a legacy IsoTP communication mode to be compatible with software using the IsoTP communication of CMM-III. The IDs for the IsoTP interface can be configured in the GUI. For further information please contact IRS.

hashtag
Revision History

Revision
Date
Author
Change Log

1.0

07.11.2023

madi1

Initial Release

1.1

13.12.2024

madi1

Refactor tool names and add document info

Getting Started

hashtag
Download IRS-CMM-xCH-GUI

You can download the latest GUI on the download page.

hashtag
IP Address

At delivery the IP address of the module is set to 192.168.222.1. You can configure the IP address in a limited range with the DIP switch on the PCB. The switches are treated as a binary number and marked with their place value (1, 2, 4). Depending on the set binary number an IP address between 192.168.222.1 and 192.168.222.7 is used. If all three switches are "off" the default IP address is used.

You can change the default IP address of the module with "Tools -> DiscoveryTool" in the IRS-CMM-xCH GUI. See CMM-xCH-GUI-Manual for details.

hashtag
Setup CAN-Bus

The Ethernet-CAN-Gateway and the two Channels are connected via CAN-FD. At delivery the CAN-FD is configured to 1000 kBit/s without bit rate switching. If necessary, the baudrate settings can be changed in the IRS-CMM-xCH-GUI. The settings can be reset to their default values with the "CAN default jumper". See CMM-xCH-GUI-Manual for more details. A single termination resistor is installed on the board and is activated with the "CAN 120R jumper". This single termination resistor is sufficient for one single CMM-2CH without bit rate switching. If you want to connect multiple CMM-2CH or use bit rate switching a proper external termination of the CAN bus with two resistors at both ends of the CAN harness is highly recommended. Without proper termination a reliable communication between the Gateway and the Channels may not be possible.

hashtag
Configure Board and Channel

Multiple CMM-xCH boards can be connected via CAN bus. To address the individual boards, each board needs to be configured with a unique Board ID.The configuration of the Board ID is done with the DIP switch on the board marked with "CAN ID". The switches are treated as a binary number and marked with their place value (1, 2, 4, ...). The switches are read at power up. So after changing the Board ID a power cycle is required.

hashtag
How to Read Measured Current Values

hashtag
Use the CMM-xCH-GUI

In the GUI switch to the tab "Measurement" and either use the Button "MIN/AVG/MAX" or enable cyclic messages. For details see CMM-xCH-GUI-Manual.

hashtag
Use the Messy CMM API

If the CMM-2CH is connected to a MesSy-II or MesSy-II-FD you can use the integrated Messy CMM API to read min, max and average values. For details see MesSy documentation.

hashtag
Directly send and receive CAN messages

You can either query min, max and average values with a CAN message or enable cyclic messages. You can use the the IsoTP protocol which is known from CMM III and CMM IV or a new protocol which is based on CAN-FD. For the details of the new protocol we can send you a DBC or SYM file on request.

hashtag
Revision History

Revision
Date
Author
Change Log

Release Notes

Clarify recommended termination of CAN bus

1.0

07.11.2023

madi1

Initial Release

1.1

13.12.2024

madi1

Datasheet

CMM-3CH-5A60V

hashtag
Description

This module offers two separately isolated channels for current measurements over a wide range from 1µA to 5A. Ethernet and CAN-FD are available for communication. Current is measured in six automatically selected ranges as listed in the table below:

Range
Lower End
Upper End
Lower Threshold
Upper Threshold

hashtag
Mechanical details

hashtag
Ambient conditions

hashtag
Current Paths

Min
Typ
Max
Unit
Remarks

hashtag
Module Supply

Connect the power supply between +24V-CON and GND-CON. It is strongly recommended not to use the DUT power supply to power the CMM. Please note that the current path is interrupted when the module is unpowered.

Min
Typ
Max
Unit
Remarks

hashtag
Typical inrush current waveform

hashtag
DC Accuracy and resolution

The module’s accuracy is verified for DC currents during in-house calibration. The module may of course be re-calibrated. See for more info.

Typ
Max
Unit
Remarks

hashtag
DC Voltage Drop

The following table lists the voltage across the module’s current input and output pins for specific current values. These are typical values, measured at room temperature at the connector pins of one channel.

Typ
Unit
Remarks

hashtag
Ethernet

The module supports 10Mbit/s and 100Mbit/s Ethernet on the RJ45 front connector. Default IP: 192.168.222.1

hashtag
CAN-FD

The module provides a CAN-FD interface on the front via a 9-pin D-Sub connector as well as on the backplane connector.

120Ω on-board termination is available via jumper. On-board termination is only recommended if a single module is used without further devices connected via CAN. If multiple devices are connected via CAN, it is recommended to use external termination on both ends of the CAN harness. This avoids problems when modules are swapped or replaced.

hashtag
Backplane connector

Connector type: Harting 09041326921 Please make sure you use all connector pins for current in / current out. A backplane-pcb is available for easy connection with just two pins per current measurement channel.

Pin
Signal
Pin
Signal

hashtag
Calibration Recommendation

IRS recommends a recalibration within 2 years.

The calibration should be performed for each channel at multiple calibration points for all 6 ranges. IRS recommends measuring at least the following currents.

Range
Calibration Points

Current values should be captured with the function (IRS.CMM-xCH.Shared.Gateway).GetMinMaxAverage. This function returns the value averaged since last read.

Before capturing a valid value, enable the calibration current, perform a dummy read and wait 100 ms.

The fluctuations of the power source used should not exceed 0.1% of the nominal value.

hashtag
Revision History

Revision
Date
Author
Change Log

10mA

0.9mA

11mA

3

10mA

100mA

9mA

110mA

4

100mA

1A

90mA

1.1A

5

1A

15A

900mA

Worst case DC current

8

A

25° Ambient Temperature with airflow >2m/s

Maximum measurable current

15

A

Single pulse current

25

A

max. 100ms

DC Current per pin on backplane connector

6

A

Voltage across current in/out when module is off

60

V

Leakage current @ OFF

100

µA

60V across module , temperature 25°C

Isolation rating

-150

150

V

Maximum allowed voltage difference between module supply and current path

Reverse current continuous

3

A

Reverse current single pulse

25

A

Max. 100ms

Supply current (Ethernet port active)

110

mA

Supply voltage = 24V

Supply current (Ethernet port inactive)

95

mA

Supply voltage = 24V

Supply inrush current

3

A

Inrush current for < 1ms @ dU/dt ≈ 20V/ms, 24V supply

0,2

1

%

% of respective range’s maximum current

Resolution range 0

40,4

nA

Resolution range 1

404

nA

Resolution range 2

4,04

µA

Resolution range 3

40,3

µA

Resolution range 4

403

µA

Resolution range 5

4,03

mA

Range 1

Drop @ 10mA

55

mV

Range 2

Drop @ 100mA

60

mV

Range 3

Drop @ 1A

60

mV

Range 4

Drop @ 10A

110

mV

Range 5

Drop @ 15A

170

mV

Range 5

CAN High

A6

Channel 0 Current In

C6

Channel 0 Current In

A8

C8

A10

C10

A12

Channel 0 Current Out

C12

Channel 0 Current Out

A14

Channel 1 Current In

C14

Channel 1 Current In

A16

Channel 1 Current Out

C16

Channel 1 Current Out

A18

C18

A20

C20

A22

C22

A24

Channel 2 Current In

C24

Channel 2 Current In

A26

Channel 2 Current Out

C26

Channel 2 Current Out

A28

C28

A30

C30

A32

C32

10 mA, 20mA, 40 mA, 60 mA, 80 mA, 100 mA

1 A

0.1 A, 0.2A, 0.4 A, 0.6 A, 0.8 A, 1 A

10 A

1 A, 3 A, 5 A, 8 A, 12 A, 15A

Updated current values, connector pinning

0

1µA

100µA

-

110µA

1

100µA

1mA

90µA

1.1mA

2

Module dimensions

160mm x 100mm (Eurocard)

19” specification

5 TE x 3 HE

Ambient operating temperature

5…50°C

Storage temperature

-20…70°C

Humidity

5…80% noncondensing

DC current

5

A

Supply voltage

20

24

26

V

Accuracy uncalibrated

0,5

2

%

% of respective range’s maximum current

Drop @ 100µA

50

mV

Range 0

Drop @ 1mA

50

Supported nominal bit rates

500 kbit/s, 1 Mbit/s

Supported data bit rates

1 Mbit/s, 2 Mbit/s, 4 Mbit/s

Default settings

1 Mbit/s nominal, 4 Mbit/s data, no bit rate switch

A2

+24V module supply

C2

0V module supply

A4

CAN Low

100 uA

1uA, 20 uA, 40 uA, 60 uA, 80 uA, 100 uA

1 mA

0.1 mA, 0.2mA, 0.4 mA, 0.6 mA, 0.8 mA, 1 mA

10 mA

1 mA, 2mA, 4 mA, 6 mA, 8 mA, 10 mA

1.0

28.07.2025

madi1

Initial Release (copied from CMM-2CH)

1.1

28.07.2025

chapter "Calibration Recommendation"
Module supply voltage (green) and supply current (red)

1mA

+24V-CON to GND-CON

Accuracy calibrated

mV

C4

100 mA

miho1

Possible Problems when using CMMs as Load Switch

Version: 1.1 | Author: madi1 | Last Update: 13.12.2024 | Revison History

hashtag
The CMMs are NOT designed to be used as load switches.

The CMMs are designed as sensitive measurement devices which can measure currents as low as 1µA. Therefore they offer little protection against voltage spikes and have no integrated freewheeling diode or other protective circuitry, because this circuitry would add unwanted measurement errors.

If you need to switch DUTs on and off, you should use a suitable load switch like a relay. A recommendation for two DUTs which are powered from the same power supply is illustrated in the image below. IRS can help you to find a suitable solution for your application and offers a load switch which can be directly connected to the CMM-3CH. Please contact IRS for further information.

If you really need to use the CMM as a switch there are at least two possible problems which should be considered:

hashtag
Max Voltage Rating could be exceeded when inductive Loads are switched off

If an inductive load is switched off, the energy stored in the load is released. This energy can cause a voltage spike which can exceed the maximum voltage rating of the CMM. The following image illustrates the problem:

If you need to switch the CMM while an inductive load is connected, you must always connect a freewheeling diode to the load to protect the CMM. Our recommendation is NOT to use the CMM as a load switch. Use a suitable load switch instead.

hashtag
Negative Spike when Power Supply is switched off while CMM is "open"

The CMMs have a built-in capacitor to smoothen current measurements. If a CMM is open, either because it is not powered or because it is switched to the "open" state, the capacitor is charged to the supply voltage. If the supply voltage is then switched off, while the CMM is still open, the capacitor remains charged and a negative voltage is seen by the DUT.

The following images illustrate the problem:

This problem mainly occurs with DUTs which have a high input impedance (for example a DUT in sleep mode) and therefore cannot discharge the capacitor quickly. The negative voltage could either damage the DUT or a connected measurement device like the MesSy-II.

hashtag
Revision History

Revision
Date
Author
Change Log

Add info about load switches from IRS

1.0

07.11.2023

madi1

Initial Release

1.1

13.12.2024

Illustration of one power supply, two DUTs and two load switches
Illustration of the voltage spike caused by an inductive load
Illustration of the negative voltage caused by swtiching a power supply while the CMM is open
Simulation result of the negative voltage caused by switching a power supply while the CMM is open

madi1

Release Notes Firmware

hashtag
V4.4 (2025-02-19)

  • Added: Support for CMM-3CH variant

hashtag
V4.3 (2024-06-18)

  • Changed: Updated GCC compiler version

  • Changed: Default values are now active directly after the command was used. No need for a reset.

  • Fixed: Bug which sets wrong data baudrate when IsoTP is used to set baudrates

hashtag
V4.0 (2023-11-28)

  • Fixed: Bug which can result in all gates switched off, when CMM is switched on

hashtag
V3.14 (2023-10-18)

  • Added: Command "ReadCurrent"

  • Added: Commands "SetTime" and "GetTime"

  • Added: Timestamp in command "ReadCurrent"

  • Added: IsoTp command "GetSerialNumber"

hashtag
V3.12 (2023-10-09)

  • Added: FIFO for IsoTP RX messages

  • Fixed: Bug which rejected padded IsoTP messages

hashtag
V3.10 (2023-09-12)

  • Added: Legacy mode for cyclic message

  • Added: Command LegacyConfig to make ID for legacy mode configurable

  • Added: FDCAN command RestoreDefault

  • Changed: Rename command IsoTpConfig to LegacyConfig

hashtag
V3.7 (2023-06-26)

  • First public release

Changed: Rename project to IRS-CMM-xCH-FW

Fixed: Bug in SaveConfiguration()

  • Fixed: Added missing flag in "send cyclic message"

  • Fixed: Bug in deserialization functions

  • Documentation of CAN messages

    CMM-2CH and CMM-3CH can be controlled via CAN-FD. Each measurement channel has its own microcontroller. The nominal baudrate is 1 MBit/s, the data baudrate is 4 MBit/s. A DBC file is available on the download pagearrow-up-right.

    hashtag
    Structure of CAN-IDs

    The CAN IDs are build with the following scheme.

    Bit
    Mask
    Content
    Comment

    The highest value of board (0xFF) and channel (0xF) is used as broadcast. For example the ID 0x 0 00 4D 01 F is the command "SetOnOff" (= 0x01) for all channels on board 1.

    hashtag
    List of CAN-Commands

    Physical values are always transmitted as float (32 Bit / Single Precision / LSB first) and in the base unit (V / A / sec / °C / ... ).

    hashtag
    CAN-IDs to set and get register style values

    Get-ID and Response-ID are the same, because the already differ in the direction bit 28. The command values in the following table include the direction bit, to make this clear.

    Set-ID
    Get-ID
    Response-ID
    Command
    DLC
    Data

    hashtag
    Status codes

    Code
    Description

    hashtag
    Values in WarningRegister

    Name
    Value

    hashtag
    Cyclic CAN-IDs uC -> PC

    Physical values are always transmitted as float (32 Bit / Single Precision / LSB first) and in the base unit (V / A / sec / °C / ... ).

    Command-ID
    Name
    DLC
    Data

    11-4

    0x00000FF0

    Board-ID

    0...31 (Can be set via DIP switch on CMM-2CH), 255 = 0xFF = broadcast to all boards

    3-0

    0x0000000F

    Channel-ID

    0...2 (Is hardwired on CMM-xCH), 15 = 0xF = broadcast to all channels

    0x001

    0x041

    0x141

    OnOff

    1

    OnOff [0/1] (U1)

    0x002

    -

    -

    OnOffSelected

    1

    EnableMask_Board (U8)

    0x003

    0x043

    0x143

    MinRange

    1

    MinRange (U8)

    0x004

    0x044

    0x144

    MinMaxAvg

    24

    CurrentMin [A] (float), CurrentAvg [A] (float), CurrentMax [A] (float),

    VoltageDropMax [V] (float), NoOfSamples (U32), RangeMin (U8), RangeMax (U8)

    0x005

    0x045

    0x145

    ChannelConfig

    5

    OnOffDefaultValue [0/1] (U1), MeasuredValuesInterval [sec] (float)

    0x006

    0x046

    0x146

    CanConfig

    3

    TxFrameFormat [Enum] (U8), NominalBaudrate [Enum] (U8), DataBaudrate [Enum] (U8)

    0x007

    0x047

    0x147

    LegacyConfig

    16

    LocalId (U32), LocalIdIsExt (U1),RemoteId (U32), RemoteIdIsExt (U1)

    LegacyCyclicId (U32), LegacyCyclicIdIsExt (U1), LegacyCyclicMessageEnable (U1)

    -

    0x048

    0x148

    Version

    12

    HardwareType (U8), FirmwareVersion (U16), CompileTimestamp (U32),

    WarningRegister (U16), HardwareVersion (U8)

    -

    0x049

    0x149

    SerialNumber

    12

    SerialNumber (String 12 Bytes)

    0x00A

    -

    -

    RestoreDefault

    0

    -

    0x00D

    0x04D

    0x14D

    DisableCalibration

    1

    DisableCalibration [0/1] (U1)

    Parameter out of range

    0xE3

    Flash error

    0xE4

    Flash verify error

    0xE5

    Command not allowed

    0xE6

    Firmware hardware mismatch

    0xE7

    File not found

    WARNING_DISABLEDCALIBRATION

    0x0010

    WARNING_ISOTPRXFIFOFULL

    0x0020

    ErrorType (U8), FileNumber (U8), LineNumber (U16), more info

    28

    0x10000000

    Direction

    0: PC to uC, 1: uC to PC

    27-20

    0x0FF00000

    Command-ID

    0...255 see section Commands

    19-12

    0x000FF000

    Module-ID

    -

    -

    0x140

    CommandResponse

    2

    0xA0

    Success

    0xE0

    Unknown command

    0xE1

    Invalid DLC

    WARNING_CANRXFIFOFULL

    0x0001

    WARNING_CANTXFIFOFULL

    0x0002

    WARNING_CANBUSOFF

    0x0004

    WARNING_INVALIDCALIBRATION

    0x180

    MeasuredValues

    12

    Current [A] (float), Range (U8), VoltageDrop [V] (float), OnOff [0/1] (U1)

    0x18E

    ErrorHandler

    "M" = 0x4D

    StatusCode (U8), Command (U8)

    0xE2

    0x0008

    48

    Downloads

    myIRS - Downloadsdownloads.irs.systemschevron-right
    Logo