Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
These instructions will ensure the safe and efficient handling of IRS EME (active motor emulator).
The instruction is part of the test system and must always be kept accessible in the immediate vicinity of the system. The personnel must read this instruction carefully before starting any work. Basic condition for safe operation is the compliance with all specified safety and operating instructions in this manual.
In addition, the local accident prevention regulation and general safety regulation for the use of the device are valid.
Illustrations in this manual, the instructions in the appendix for the installed components apply.
Following the instructions given in this manual helps to avoid dangers and to increase the reliability and lifetime of the device.
We accept no liability for consequential damage and accept no responsibility for damage to property or injury to persons caused by improper operation or failure to observe the safety instructions. Such cases void the guarantee.
If you have any questions that are not answered by this instruction, please contact:
IRS Systementwicklung GmbH
Pfaffenthanner Weg 5 D-93179 Brennberg +49 (0) 94 84 / 95 00 – 0 www.irs.systems
Safety instructions
DANGER!
… indicates an imminently hazardous situation that will result in death or serious injury if not avoided.
WARNING!
… indicates a potentially hazardous situation that may result in death or serious injury if not avoided.
ATTENTION!
… indicates a potentially hazardous situation that may result in minor injury or property damage if not avoided.
Special Safety instructions
To draw attention to special risks, the following symbols are used in safety instructions:
DANGER!
Danger to life due to electric current!
… features life-threatening situations by electricity. Non-observance of the safety instructions can result in severe injury or death.
All information and instructions in this manual have been compiled in accordance with applicable standards and regulations, the prior art as well as our many years of knowledge and experience.
The manufacturer assumes no liability for damages resulting from:
Ignoring the instructions
Improper use
Use of untrained personnel
Unauthorized modifications
Technical changes
Use of unauthorized spare parts
The actual scope of delivery can vary for special designs, utilization of additional order options or because the latest technical changes from the explanations and representations described here.
Valid are in the delivery contract agreed obligations, the terms and conditions as well as the manufacturers delivery terms and at the time valid legal regulations.
We reserve the right to make technical changes in the context of improving the usage properties and further development.
WARNING!
Safety risk by inappropriate spare parts!
Wrong or faulty spare parts can affect the safety and result in damage, malfunction or failure.
Therefore:
Use original spare parts from the manufacturer only.
Obtain spare parts from authorized dealers or directly from the manufacturer of each component.
For technical information contact our customer service.
In addition, our employees are always interested in new information’s and experiences arising from the application and for the improvement of our products.
The following general safety precautions must be observed during all phases of operation of this instrument. Failure to comply with these precautions or with specific warnings or instructions elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. IRS Systementwicklung GmbH assumes no liability for the customer’s failure to comply with these requirements.
The device is used in the industrial sector. Therefore, the operator is subject to the legal responsibilities for workplace safety.
In addition to safety instructions in this manual, the operator must comply with general safety, accident prevention and environmental protection requirements. These are especially:
The operator must be aware of the applicable health and safety regulations and in a hazard assessment other hazards that may result from the specific conditions at the site of operation. This must be implemented for the operation of the device in the form of operating instructions.
The operator must clearly regulate and specify the responsibilities for installation, operation, maintenance and cleaning.
The operator must ensure that all employees who handle the unit, have read and understood the operating instructions. In addition, he must train regularly and inform the personnel about the risks.
The operator must provide the required personnel protective equipment.
Furthermore, the operator is responsible for ensuring that the equipment is always in perfect condition, therefore the following applies:
The operator must ensure that the maintenance intervals described in this manual are adhered.
The operator must check all safety devices for functionality and completeness regularly.
WARNING!
Risk of injury due to insufficient qualifications!
Improper use may result in serious personal and material damage.
Therefore:
All work carried out only by qualified personnel.
Personnel
(according BGV A 3)
Nominated person in control of an electrical installation
is a person who is authorized to take the responsibility of the electrical establishment. If necessary, the responsibility can be partly given off to other persons.
Electrically qualified person
is a person who is capable to estimate potential risks due to his expertise, experience and knowledge of corresponding assignments.
Electrically instructed person is one who has been taught by a qualified electrician over its assigned tasks and the potential hazards of improper behavior required, trained and have the necessary safety devices and protective measures.
The EME active motor emulator is designed and constructed exclusively for the purpose described herein:
Testing of inverters, not exclusively, but mainly for e-mobility applications like traction inverters of electrical vehicles. The device under test (DUT) may run under specific parameters like heat, cold, humidity, vibration, salt spray or others. The Emulator itself runs in industrial plants at room temperature at normal humidity without environmental stress.
The emulator performs the following functionality:
Simulation of the vehicle electrical system from the DUT point of view:
Motor phases
Battery power supply (in combination with external DC power supply)
Position sensor input signals (e.g. SIN/COS or Resolver)
Monitoring of voltages and currents which are applied to or output from the DUT
Provision of measurement data to the overall system.
WARNING!
Danger from improper use!
Do not use this product in any manner not specified by the manufacturer. The protective features of this product may be impaired if it is used in a manner not specified in the operation instructions.
Other than under the "Intended Use" specified or beside this all usage is considered as improper use! Claims of any kind for damage resulting from improper use are excluded. The operator is liable for all damages resulting from improper use.
The following safety instructions and warnings in the other chapters of this manual should be observed to reduce health hazards and avoid dangerous situations
DANGER!
Danger to life due to electric current!
In case of contact with live parts there is immediate danger to life. Damage to the insulation or individual components can be highly dangerous.
Therefore:
In case of damaged insulation immediately switch off the voltage supply and arrange the repair.
Work on the electrical system may only be made by qualified electricians.
When working on the electrical system, switch off the power supply and verify voltage freedom.
The system is equipped with an UPS (Unbreakable Power Supply) always switch off the UPS before performing any maintenance
Before performing any maintenance, cleaning and repair switch off power supply and secure against restart and disconnect tester from line supply
Do not bridge fuses or put out of operation. When replacing fuses comply with the correct amperage.
Keep moisture away from live parts. This can lead to short circuits.
WARNING!
Beware of the health and environmental risk of glycol coolant mixture
Coolant mixture may never be inhaled or swallowed or get in contact with eyes
Avoid contact with your body or skin.
If you were in contact with glycol, wash yourself properly.
Coolant mixture may never get into the environment
Make sure that spilled coolant mixture is properly wiped away and dispose the cloth appropriately.
Preventive measures
Always be prepared for accidents or fire!
First-aid equipment (first aid kit, blankets, etc.), and fire extinguishers retain for future use
Make personnel familiar with accident reporting, first aid equipment and rescue measures.
Keep access routes for emergency vehicles clear.
Measures in case of accidents
Trigger emergency stop
First-aid measures should be considered.
Recover people from the danger zone
Inform the responsible person on site.
alert emergency services
Keep access routes for emergency vehicles clear.
Following block diagram gives an overview of a typical inverter test setup from the point of view of a single device under test (DUT):
The central item in the picture is the inverter, the device under test (DUT), which is electrically connected to:
Power supplies, communication interfaces, miscellaneous sensors
The HV battery
the electrical motor via typically 3 motor phases
and its position sensor
For inverters for power ranges of several kilowatts water cooling is usually applied.
The yellow marked parts are covered by the IRS EME active motor load:
synchronous motor
position sensor
and partially the HV battery in combination with a standard DC power supply.
To simulate the motor, there are generally different approaches commonly used:
Simulation of a simple passive load
Operation of a real motor, mechanically coupled with another motor-inverter-combination
High-end motor simulators
The following table shows the advantages and disadvantages of these setups:
✅ Very cost-efficient
⛔️ Very high price
⛔️ Very high price
✅ Small setup
⛔️ Space consuming setup
⛔️ Space consuming setup
✅ Full phase current
✅ Full phase current
✅ Full phase current
⛔️ Only reactive phase current
✅ Simulation of real phase currents
✅ Simulation of real phase currents
⛔️ No recuperation
✅ Recuperation possible
✅ Recuperation possible
🔶 Low DC currents
🔶 Real DC current from battery
🔶 Real DC current from battery
IRS EME active motor load is a solution which combines advantages of full-size high end motor simulators with the advantages of the passive coil, by keeping the concept simple, reliable and at a low cost.
🔶 Cost efficient
✅ Small setup
✅ Full phase current
✅ Simulation of real phase currents
✅ Recuperation possible
✅ Real DC current, but low power
To simulate a real load condition the induced voltage of the electrical motor needs to be generated, according to the equivalent circuit of a motor:
Voltage sources for high power are often also switched power supplies, while a good energy feedback is necessary to achieve a compact and cost-efficient setup.
Following picture shows the basic setup of the IRS electrical motor emulator for a three-phase-inverter as device under test (DUT):
The concept is based on the idea to directly couple two inverters and run against each other - both three phases and the DC-Link are directly coupled. As battery simulator a standard power supply may be used. With appropriate control of the motor simulator, the phase current flows from DUT to simulator via the phase coils and back to the DUT via the DC-Link, and vice versa.
Thus, the DC-Link of the DUT is stressed with a realistic current, but since the energy is flowing between the two inverters, the battery simulation needs only to provide the energy for the losses of the entire system. This is one of the most important benefits: a relatively small power supply without energy feedback to the grid can be used. With a power supply of only 20kW,
250kW can be simulated at 500V DC voltage,
350kW can be simulated at 850V DC.
The standard emulator variant is capable of handling voltages up to 1000V, resulting in even higher power ranges which can be simulated. In most setups, three basic setpoints define the operation:
EME generates the induced voltage of the motor
DUT is in current control mode, defining the applied torque to the motor.
EME defines the speed via the position sensor signal
In this document, we mostly refer to the voltage range up to 1000V, since this is covered by the standard IRS EME. In the meantime, different downsized variants are available which will be illustrated in later chapters. But the basic principle is the same for all IRS EME variants.
Electric Motor Emulator for inverter testing with active load
EME 1x 3-phase (W x D x H)
1x VARIS II
800 x 900 x 2050
mm
EME 2x 3-phase (W x D x H)
2x VARIS III
1200 x 900 x 2050
mm
Weight approx..
1x VARIS II / 2x VARIS III
500 / 800
kg
Temperature range
5-35
°C
Relative humidity
max 31 °C: 80
%
max 40 °C: 50
%
No condensation
Setup
in dry laboratory rooms
altitude above sea level
max. 2000
m
AC Input
Supply voltage
100…240
Supply frequency
50/60
Tester electronics supply
Max. Current
6
Typ. 0,5
kVA
DC-Supply
DC supply voltage
0…1000
DC supply current
(Depending on use-case)
-150…150
In the following sections, the maintenance is described, which is required for optimal and trouble-free operation. If you have questions about maintenance work and intervals contact the manufacturer. Connections for higher currents must be checked for clean contacting and mechanical strength (tensile test).
High current contacts
motorphases
9
X
X
Check proper connection of the ring-lugs. Do the ring lugs lie flat on the contact area? Are the nuts pulled tight? Do a manual tensile test on the cable.
High current contacts HV DC
12
X
calibration
1 set
According
To aggreement
Typ. 1..3 years
EME calibration needs to be done on site with calibration kit.
EME internal cooling circuit
3
x
X
Check water pressure at manometer (see chapter 11.1.1). ggf. nachfüllen (siehe Kapitel 11.1.2)
If the internal pressure drops below 1 bar, the internal cooling circuit must be refilled. To do so, connect a tube with ½“ fitting to the refill connection (see picture above) and fill with a water/glycol mixture with a pressure of at least 3 bar.
Optimum mixture is:
25% glycol
75% clean water
Open the valve behind the refill connection to let water/glycol mixture flow into the internal buffer. Close the valve when the manometer shows 2,5 bar. Disconnect the filling tube, and clean remnants of eventually spilled water/glycol.
WARNING!
Beware of the health and environmental risk of glycol coolant mixture
Coolant mixture may never be inhaled or swallowed or get in contact with eyes
Avoid contact with your body or skin.
If you were in contact with glycol, wash yourself properly.
Coolant mixture may never get into the environment
Make sure that spilled coolant mixture is properly wiped away and dispose the cloth appropriately.
Switch off system bevor cleaning, service and maintenance and measures and secure against immediate restart.
Cool off system before cleaning and service.
The surface of devices can be cleaned with a damp cloth.
If water or is present in the drip pan, absorb it with a dry cloth.
The following figure illustrates the connections which need to be established from and to EME. These are:
connections to the allover test system (left side in the picture).
connections to the inverter under test (right side).
The active motor simulation is using water cooling.
An inlet temperature of about 15°C is recommended (10…25°C). Keep cooling water clean, filters are recommended to avoid remnants in the heat exchanger which reduce the cooling capacity.
A flow limiter should be added to define the water flow. Flow rate is depending on average and peak power. Typical values are 5…30l/min. please monitor the EME temperatures as shown in chapter 4.4.2.1.
Make sure that cooling water is only applied when necessary to reduce the amount of condensing water.
For proper operation the active motor load requires connections to the overall test system. The figure in chapter 6 illustrates the test system connections on the left side, while red marked wires contain hazardous voltages. The blue marked lines correspond to the cooling tubes.
Connections are designed with modular Harting connectors as far as possible to make sure that no wrong connections can be established. Furthermore, the same connectors may be used for different international standards. Connector counterparts are delivered together with the system.
All connections are available at the top of the cabinet.
Safety + electronics supply
The following Harting HAN-connector is applied for connection to the HVDC power supply.
Pinout is as follows:
Pin1 HVDC+
Pin2 HVDC-
Both male and female connectors are protected against direct contact. This is necessary because the active load buffer capacitors may be charged even when disconnected.
The following Harting HAN-connector is applied for connection to the electronics supply and the safety interface. The pinout is as follows:
On the right side the functionality of the safety interface is illustrated, both for switches and the analog output for DUT voltage measurement.
Use the Ethernet cable with RJ45 connector for communication with a Windows-PC.
Currently not applied in software.
After the tester internal connections are ready, the wiring to the DUT needs to be established. The figure in chapter 6 illustrates the DUT connections on the right side, while red marked wires contain hazardous voltages. The blue marked lines correspond to the cooling tubes.
SIN/COS Simulation
1
GMR_SIN_P
7
AMR_COS_P
2
GMR_SIN_N
8
AMR_COS_N
3
GMR_COS_P
9
--
4
GMR_COS_N
10
--
5
AMR_SIN_P
11
--
6
AMR_SIN_N
12
GND
Please refer to chapter 4.2.1 for functional description
Resolver Simulation
Pin
Signal
1
SIN+
2
SIN-
3
COS+
4
COS-
5
EXC+
6
EXC-
Please refer to chapter 4.2.2 for functional description
Motor phases, HV-DC supply and exciter wires are connected according to the picture below. Preferred, the cables are marked with the following labels to make sure not to mix them up:
U V W
DC+ DC-
Always apply shielding clamps and strain reliefs similar to the following picture:
Since there are several wires for three DUTs, it is be a good choice also to mark the wires with DUT1, DUT2, DUT3.
WARNING!
Always make sure to establish low impedance connections:
ring lugs must lie flat on the current bars!
Do NOT use washers in between ring lugs and current bars!
Use an appropriate torque wrench to fix the wires with
30Nm for the motor phases and HV-DC+/-.
15Nm for the exciter connection
WARNING!
Always make sure to reduce EMC noise:
The shielding of the motor phases must be properly connected to the shielding rail with EMC-shielding clamps.
For this purpose, the outer isolation of the motor phase wire has to be removed in the area of the shielding clamp. The shielding clamp is pushed over the open shielding and is linked on the shielding rail.
The same procedure with shielding clamps and strain relief holds for the Exciter and HV-DC connections.
Additional to the EMC-shielding clamp, a strain relief has to be mounted in the lower part of the shielding rail. The same procedure with shielding clamps and strain relief holds for the Exciter connections.
WARNING!
Always make sure to connect all DUT connections are fitting to the dedicated pin. Otherwise, the DUT or the system may suffer damage:
Interchanged motor phases may lead to inacceptable high phase currents on single phases and may cause overload on DUT or emulator
Interchanged HV-DC-connection result in short circuit of the HV-power supply. This is clearly visible, when the HV supply is active, in current limit and the voltage remains below 10V.
Since the DUT inverter may be a source of electrical noise, measures need to be taken to reduce emissions from the DUT. Most emissions are radiated over the motor phase cables. Thus, special care needs to be taken about:
Proper Shielding of motor phase, HV-DC-, and Exciter-cables
Proper grounding of the DUT and test system.
Positioning of power and signal cables
When operating the system, it is crucial that all power cables are properly shielded on BOTH ends. I.e.
At the emulator connection
At the DUT-housing
Use shielding clamps at the emulator connections:
Make sure that all power cable shields are properly connected to the DUT housing by metal bushings:
To make sure, that the DUT housing as a proper ground connection, establish an additional ground wire to a good potential earth Ground.
And keep as much distance as possible between signal cables and power wires to reduce cross interference. If there is not enough space, avoid routing them in parallel, prefer orthogonal orientation.
After connecting all system components and the DUTs, and after power up, the motor emulator may be operated by software either manually by a remote panel but for most test systems by an automation software.
The Emulator comes by default with a LabVIEW library “IRS.EME.TS.API” including dependencies for integration in user specific automation software.
Alternatively, the user may use low-level TCP-IP communication with a command-response structure, based on JSON command description (see “EME Example Communication.txt”).
A test panel is provided to control EME manually. It contains most control functions of the LabVIEW library. Thus, in the following software functions are explained based on the test panel because of good illustration. The explanations for the test panel may be transferred to operation with automation software.
The „EME_RemotePanel“ software may be used to control EME manually. It may be opened in parallel to the automation software.
The panel includes up to 8 functional sub-panels and controls to handle the IP-connection.
System: general status (software version, temperatures, CPU-load)
Config: general configuration (motor and sensor parameters)
Control: operation parameter (“induced voltage”, speed,…)
Function: operation parameter for fixed position
Streaming: waveform measurements
Errors: indicates error flags
ICTRL: advanced settings for inverter operation, not for emulator.
IRS: critical and advanced parameters only accessible by IRS
The respective functional sub-panel may be selected in the control “Testpanels”.
The following controls and buttons are used for connection handling
IP-Address: identifies a specific EME in the network
Scan: searches for visible EME in the network
Connect: establishes communication with one EME
Disconnect: stops communication with one EME
Log: shows communication status with EME
orange items show errors
There may be several EME in one ethernet network. The respective EME is addressed by his IP-Address. You may either enter the known IP address directly in the yellow marked field:
Alternatively, you may search for existing EME in the network. By pressing the following two yellow marked buttons:
After pressing the “Connect” button all other functions in the sub-tabs are available.
After pressing “Disconnect” no operation is possible.
In the Log window the communication status is listed:
Connect event
Disconnect event
Errors (marked in orange with error description)
The log window may be cleared with the button “Clear Log”.
After pressing the “STOP” button, the test panel will close.
In the system status overview the following parameters are shown:
General information:
Software versions of
EME-API (LabVIEW-library on PC)
RT-Software (real-time firmware on EME)
FPGA (lowest level firmware on EME)
Control board
HW-version
Serial number
Internal temperatures
Temperature values of EME
Temperatures of “Opponent”
in case of combined 6-phase system.
In most cases all “Opponent” values may be ignored.
CPU load
Operating times of
sbRIO (real-time controller + FPGA running time)
EME (powered operation time while EME is active).
In the Config sub-panel, generic motor and position sensor parameters may be set. The order of configuration is not relevant. Settings in this window may be changed at any time while EME is not activated.
The configuration parameters on the left side describe the motor parameters and are as follows:
Set Role
“Single” for normal Emulator operation -> valid for most application
“Inverter Single” for Inverter operation -> typical use-case for sensor calibration
…Master/Slave… Master- and Slave-Configurations are only used for 6-phase-systems. Please contact IRS for simulation of 6-phase motors.
Set DUT Parameter
“SPWM” pure sinusoidal modulation (usually not used)
“SVPWM” standard Space-Vector-PWM (standard setting).
Set Motor Parameter
Polepairs: number of motor pole pairs (typical 3…4, must be >= 1)
Offset: Theta offset of position sensor (Range +-1 for +-180°)
Angular Displ (6ph): only used for 6-phase motors (0 by default)
Set Transition
Smooth Transition should always be enabled to avoid too fast change of modulation.
Slope [delta/10µs] typical value in the range about 10-4…10-7
Set Network Parameters
Resistance [Ohm]: typical resistance of the setup (200µ … 1m)
Inductivity [H]: typical applied inductance (85µH)
The configuration parameters on the right side describe the position sensor parameters and are as follows:
Set xMR Parameter
Offset: DC voltage of SIN/COS sensor signals (typical 2,5V)
Amplitude: amplitude of SIN/COS sensor signals (typ. 2V)
Set xMR Multiplier
AMR/GMR_SIN/COS_P/N: factor between mechanical frequency and SIN/COS Signals (typ. 1…3)
Set Resolver Parameter
Transfer Factor: quotient between sine or cosine max. amplitude to excitation amplitude
Calibration: usually default values (100%, 0°)
Sine Amp [%] correction factor in case of symmetry difference
Cosine Amp [%] correction factor in case of symmetry difference
Phae Correction [°] phase shift correction between sine and cosine
Set Sensorless Enable
Enable sensorless mode: if set to True, the emulator ignores position sensor. And calculates current position from DUT PWM. Position sensor signals are generated nevertheless.
In the “Control” sub-panel, EME may be activated and the operation points may be set.
Set Interlock On/Off
Prepare EME for activation
When set, some general parameters like “Role” may not and can’t be changed!
Set Inverter On/Off
When set, EME is activated:
It starts synchronization to the DUT in case of emulator modes
In Inverter role, it immediately activates the outputs to control current on the motor load
The feedback flags
“PWM sync”
is immediately activated
and remains active until “Set Inverter On/Off” is reset by the user.
It indicates that EME “should be active”
“Inverter On/Off”
remains activated, as long as there is no error condition.
I.e. it is reset as soon as an error occurs.
Set Space Vector
Sets the “induced voltage of the motor” relative to DC-link-voltage.
Only use quadrature; do not use direct, because this leads to unnormal phase shifts.
I.e. if quadrature set to 0
there is no induced voltage from the motor
no real power simulated
I.e. if quadrature set to 0.9
maximum induced voltage of the motor (90% of available DC-Voltage ½ )
maximum real power is simulated
the limit of this parameter is 0.9.
Set Speed:
Defines both
position sensor signal frequency
is generated independently from EME activity
both for resolver and SIN/COS
motor output frequency
Typical values are 0…500Hz.
The motor output frequency is calculated as speed * polepairs.
Set DUT Current
Reserved, currently unused parameter.
Sub-panel “Functions” contains the following two functionalities:
AutoSync Enable
Set to True to enable easy synchronization.
Explanation for this function see chapter 4.6.
Set Stop Rotation
Stop Rotation:
False: rotation motor is being simulated
True: motor at fixed position is being simulated
Theta [-180…+180°]
In case of stopped rotation, this position will be set.
Please note that the simulation may only move to the selected position, when speed is non-zero!
By using the “Streaming” sub-panel waveforms may be captured from EME. Waveform streaming is started after:
Start Stream
button is pressed -> window appears to adjust streaming sampling rate
100kS/s is the maximum sampling rate,
10kS/s is mostly sufficient and leads to higher performance on the PC.
When stream is active, different waveforms may be selected:
With the LabVIEW API the user may additionally:
Continuously stream data to file (TDMS format)
Get characteristic values from stream (RMS phase currents, DC-voltage,…)
See “Eme_STREAMING_MemoryStream_GetChannel_TS.vi”
The waveforms have the following meaning:
I_U/V/W1
phase currents of inverter phase U, V, W
positive values mean direction into EME
negative values out from EME
The waveforms have the following meaning:
I_PS
DC current from HV power supply
I_DUT
DC current to DUT
Positive values mean motor operation of EME
Negative values indicate recuperation operation
I_d/q
Calculated value from phase currents in d/q-direction
I_Exc
Optional exciter current for simulation of externally excited motors
U_DC
DC-Link voltage
DC_U/V/W1
When EME is active: Duty cycle generated by EME on motor phases U,V,W
When EME is inactive: represents a “theoretical” duty cycle, which would be applied when EME would be active
DC_DUT_U/V/W1
Measured duty cycle from DUT
Theta_mech
Current mechanical position
Theta_el:
Current electrical position ( = mechanical position * polepairs)
I_U/V/W2
Reserved for 6-phase systems
I_EME_1/2
Reserved for 6-phase systems
“Errors” sub-panel indicates errors, which may occur:
With the button “Reset Errors” errors flags may be reset as soon as the error is not present anymore. The error flags indicate:
Safety:
Period out of range:
There was no PWM-signal from DUT
either on specific phase U,V,W or on any phase
Overcurrent Phase U/V//W
Software overcurrent shut-down
current on respective phase exceeded +1000A or -1000A.
one sample (10µs sample time) is sufficient to trigger this error.
DCLink_Undervoltage
The DC link voltage fell below configured limit.
The limit is configured in EME and may be adapted by IRS.
IGBT Phase U/V/W High/Low side:
If this error occurs, there is a hardware damage on IGBT power switch.
Power stage must be repaired.
Overcurrent (</> 1000A) Phase U/V/W/Inverter/DUT/Rotor
Indicates that the HW overcurrent shutdown has been triggered by the respective current sensor
There is a separate indicator for every phase and polarity
Overcurrent Sum Current
Software overcurrent detection for sum current of motor phases
Any Temperature
… Warning: any temperature sensor (see chapter 8.2.2) exceeded warning limit
… Error: any temperature sensor (see chapter 8.2.2) exceeded error limit
The limits are configured in EME and may be adapted by IRS.
…Opponent:
All error flags from second linked EME - reserved for 6-phase systems
The sub-panel „ICTRL” may be used for inverter operation. It contains settings for using EME in current controlled mode.
The following parameters need to be set for inverter operation:
Set ICTRL Frequency switching frequency in Hz
Set PWM Type
SPWM sinusoidal modulation
SVPWM standard space-vector-PWM
Set CTRL parameters
ICTRL_PI_Kp: proportional value of current controller
ICTRL_PI_Ki: integral value of current controller
ICTRL_Overshoot: max. difference between setpoint and actual current
Set ICTRL active/inactive
When False:
use direct modulation via space vector d and q component
When True: use
Set Voltage Setpoints
Sets the “induced voltage of the motor” relative to DC-link-voltage.
Only use quadrature; do not use direct, because this leads to unnormal phase shifts.
I.e. if quadrature set to 0
there is no induced voltage from the motor
no real power simulated
I.e. if quadrature set to 0.9
maximum induced voltage of the motor (90% of available DC-Voltage ½ )
maximum real power is simulated
the limit of this parameter is 0.9
identical parameter as in chapter 8.2.4 (control sub-panel)
Set Current Setpoints
Sets the phase current to control in direct and quadrature direction in A
Set EME Standalone
Should be always active (default setting)
Only used for IRS
Furthermore, the same buttons and controls as in “Control” sub-panel are visible for easy operation (Set Interlock On/Off, Set Inverter On/Off, Set Speed, Reset Errors).
In the following chapter typical programming flows are described for normal Emulator and Inverter operation.
The following figure illustrates a typical programming flow for inverter operation, especially as it is used for current sensor calibration of the DUT.
The following steps and parameters show a typical setting for inverter operation, especially for current sensor calibration, where DC currents are applied on the motor phases.
In the table,
Absolutely necessary commands/parameters are marked in yellow and blue for environment
recommended parameters are marked in green, they are set by default.
while others are not relevant.
The order in the table should be regarded as order of commands, which should be sent one after another to EME.
Italic steps are environment settings. Bold written command name can be found in the JSON communication description file:
Setup
Setup environment
Connect Passive load
short EME output via DUT in active short circuit, while HV-DC supply of DUT is disconnected.
Disconnect DC from DUT
Connect EME
IP-Address
Default = 192.168.222.5
EME configuration commands:
SET_Role
Inverter Single
SET_DutParameter
SVPWM
SET_MotorParameter
Polepairs = 1
Default parameter, other values possible
SET_MotorParameter
Offset Theta = 0
SET_MotorParameter
Angular Displ. = 0
SET_SetpointTransition
True @ 1e-6
Other value possible
SET_CouplingNetworkParameter
R=0.001,
L=85e-6
Default parameters, recommended for
standard setup
SET_ICTRL_DUT_PWM_TYPE
SPWM
Default parameters, recommended for
standard setup
SET_ICTRL_DUT_Frequency
8000
Default parameters, recommended for
standard setup
SET_ICTRL_EME_CTRL_Param
Kp=0.3
Ki=0,00025
Overshoot=250
Default parameters, recommended for
standard setup
SET_ICTRL_EME_Enable_CTRL
True
Must be active for current control
SET_ICTRL_Setpoints
direct=quadrature=0
Must be 0 before activation
SET_EME_Standalone
True
Default, must be True
SET_ManualRevolutionSpeed
60
Other value possible, typ. 0…200
SET_StopRotation
False
Must be false for rotating operation and sync.
Activate Environment
Activate HV-Supply
200V
Must be above undervoltage limit
Activate Cooling
Typ. 5…10 l/min depending on current profile
Activate EME
ERROR_ResetError
none
Action without parameters
SET_Interlock
True
ACTION_PwmSync
True
From now on, EME output is active and may be operated at different setpoints.
Operate
The following steps may be executed at any time during operation.
Operate rotation and apply current:
SET_ManualRevolutionSpeed
60
Other value possible, typ. 0…200
SET_ICTRL_Setpoints
Direct = 0
Quadrature = 0…600
Please make sure that proper water cooling is active when applying currents >50A!!!!
Operate at fixed position (necessary for current sensor calibration) while applying current:
SET_StopRotation
True
Theta = -180 … 180
Typical current sensor calibration positions:
0° / -120° / +120°
SET_ICTRL_Setpoints
Direct = 0
Quadrature = 0…600
Please make sure that proper water cooling is active when applying currents >50A!!!!
Reading measurement values from streaming data is available with LabVIEW library.
Cleanup
Deactivate EME
SET_ICTRL_Setpoints
Direct = 0, Quadrature = 0
ACTION_PwmSync
False
SET_Interlock
False
Cleanup Environment
Shutdown HV-Supply
0V
The following figure illustrates a typical programming flow for emulator operation. After configuration of EME and DUT, the synchronization of EME to DUT must happen. Afterwards the user may run a current profile, while EME parameters may be kept constant of may be changed at any time.
The following steps and parameters show a typical setting for normal emulator operation. In the table,
Absolutely necessary commands/parameters are marked in yellow and blue for environment
recommended parameters are marked in green, they are set by default.
while others are not relevant.
The order in the table should be regarded as order of commands, which should be sent one after another to EME.
Italic steps are environment settings. Bold written command name can be found in the JSON communication description file:
Setup
Setup environment
Connect DUT Hardware
(phases, DC, position sensor, communication LV-supply)
Wrong connections may lead to critical currents and damage.
Connect EME
IP-Address
Default = 192.168.222.5
EME configuration commands:
SET_Role
Single
SET_DutParameter
SVPWM
SET_MotorParameter
Polepairs = according to DUT
Default = 1
SET_MotorParameter
Offset Theta = accord. to DUT
Default = 0
SET_MotorParameter
Angular Displ. = 0
SET_SetpointTransition
True @ 1e-6
Other value possible
SET_CouplingNetworkParameter
R=0.001,
L=85e-6
SET_EME_Standalone
True
Default, must be True
SET_ManualRevolutionSpeed
60
Other value possible, typ. 0…200
SET_ManualSetpointDq
Direct=0, quadrature=0.05
Should be low, but q > 0 is recommended
SET_AutoSyncEnable
True
Enabling is recommended.
If DUT increases its duty cycle slowly before synchronization, it may also be set to False.
SET_StopRotation
False
Must be false for rotating operation
and during synchronization.
EME configuration commands depending on position sensor, either SIN/COS, resolver or sensorless.
In case of Resolver:
SET_ResSiParameter
TransferFactor = 1,
SineAmplitude = 100 [%]
CosineAmplitude = 100 [%]
PhaseCorrection = 0 [°]
Parameters according to DUT resolver parameters.
Here, default parameters are shown
In case of SIN/COS:
SET_AMRGMRParameter
Offset = 2.5
Amplitude = 2.0
Parameters according to DUT sensor parameters.
Multiplier defines the ratio of signal frequency to mechanical speed.
SET_AMRGMRMultiplier
GMR_SinP_Multiplier = 1
GMR_SinN_Multiplier = 1
GMR_CosP_Multiplier = 1
GMR_CosN_Multiplier = 1
AMR_SinP_Multiplier = 2
AMR_SinN_Multiplier = 2
AMR_CosP_Multiplier = 2
AMR_CosN_Multiplier = 2
Parameters according to DUT sensor parameters.
Multiplier defines the ratio of signal frequency to mechanical speed.
Activate Environment
Activate HV-Supply
According to DUT volt.
Must be above undervoltage limit, dep
Activate Cooling
Typ. 5…10 l/min depending on current profile
Activate DUT
After this step, DUT must activate PWM output
Activate EME
ERROR_ResetError
none
Action without parameters
SET_Interlock
True
ACTION_PwmSync
True
Must be activated before DUT duty cycle is too high.
From now on, EME output is active and may be operated at different setpoints.
Operate
The following steps may be executed at any time during operation.
Operate rotation and apply current:
SET_ManualRevolutionSpeed
60
Other value possible, typ. 0…200
SET_ManualSetpointDq
Direct=0, quadrature=0.1…0.9
Higher quadrature -> means higher induced voltage -> higher real power -> higher DC-current.
Set DUT current
+-600A
Within the possible power ranges of the system!!
Negative current setpoints usually result in recuperation operation.
Both d- and q-current may be applied, while q-current leads to real power and higher DC-current.
Reading measurement values from streaming data is available with LabVIEW library.
Cleanup
Deactivate EME
Set DUT current
0
ACTION_PwmSync
False
SET_Interlock
False
Cleanup Environment
Shutdown HV-Supply
0V
Every single EME covers a 3-phase system. Two identical EME may be optionally combined to simulate a 6-phase motor, where one system acts as master and one as slave.
Every IRS EME active motor load contains a 3-phase two-level inverter, while different technologies are applied:
VARIS - versions: IGBT (Standard device)
SiC - version SiC-MOSFET (In development)
Different variants are available to cover different types of inverters:
Maximum current is depending on the applied DC voltage and switching frequency. The following diagram illustrates the dependency for example VARIS III:
By default, IRS EME comes with an 8 channel SIN/COS signal generator to simulate AMR/GMR position sensors.
The following pictures illustrate the typical signal levels, depending on the current position in degree. For aclear view, only 4 signals are shown in a single picture. The first one shows non-inverted SIN and COS for GMR and AMR (please note that some inverters use only the GMR-signals):
GMR-signals synchronous to mechanical speed:
AMR-signals synchronous to DOUBLE mechanical speed:
Optionally, an additional module may be plugged in to simulate resolver position sensors.
All inputs and outputs are isolated by transformers, as it is the case in real resolver sensors:
Excitation signal + and - input: generated by the DUT (typ. 10kHz)
SIN + and SIN – output: modulated by resolver simulator is feedback to the DUT
COS + and COS – output: modulated by resolver simulator is feedback to the DUT
There are basically two components of measurement equipment, which need to be address via Ethernet. These are:
EME control board
EME switch and cooling controller
Basically, any IP-address may be configured, but after delivery the following default IP addresses are configured:
In case, EME is applied in a system with several DUTs, the numbers in the IP-Address are incremented for every test station.
The following measurements are conducted by the active motor load EME:
All yellow marked measurements are conducted by the EME controller board, and can be read out by the LabVIEW library via Ethernet. These signals are sampled at a sample-rate of 100kS/s:
3x phase current measurement (+-1000A)
1x HV DC voltage measurement (0…1000V)
1x HV current measurement to DUT (+-600A)
1x HV current measurement from HV power supply (+-200A)
1x Exciter current measurement (optional) (+-50A)
The voltage measurement after the DC-Main relay is usually evaluated both by safety circuit to detect if there is a hazardous voltage on the DUT and optional additional measurement equipment. EME includes a voltage transducer with an adjustable output signal, marked in green. By default, 4…20mA are output representing the HV voltage at the DUT of 0…1000V.
Finally, motor phases U, V, W PWM timing is monitored with a resolution of 50ns.
The following internal temperatures are monitored with a sample rate of approximately 5 S/s.
The temperatures must remain below the following maximum values:
The following measurements and controls are conducted by the EME switch and cool unit.
Depending on T_VARIS and T_Exciter the cooling pump is automatically activated and controlled
Gigabit-Ethernet is the main communication interface which is accessible via the provided LabVIEW library.
Physically available, but currently not implemented in software.
When EME is operated normally, it synchronizes its output stage to the switching parameters of the DUT. The following chapter describes this synchronization mechanism.
Auto-Synchronization!
The following figure illustrates the safety interface:
An external safety controller MUST implement the following functionalities:
It MUST shut down external -Supply immediately in case of
EME Door Open
EME Discharge Overtemperature
EME Discharge Active
EME-discharge MUST be DE-activated in case of:
HV-Supply applies a voltage > 20V
EME-discharge MUST be activated in case of
Any error
BUT only when HV-Supply is shut down.
The following table illustrates the different situations, where the discharge control signal is inverted:
Common safety controllers operate on 24VDC. External Discharge Control signal should be controlled by 24VDC. See the following chapters about electrical parameters and connector pin-out.
Furthermore, a voltage converter is integrated which can be used by the safety controller to monitor the DUT voltage, and lock doors if voltages >50V are applied.
By default, the voltage converter outputs 4…20mA, which represents 0…1000V at the output to the DUT.
An Isolation monitor (e.g. Bender ISO-685) is necessary to monitor the isolation of HV+ and HV- against earth ground, because usually for inverter testing an IT-system is implemented.
In default configuration the HV supply and isolation monitor are not integrated into the emulator. But in case the HV supply is integrated into the emulator cabinet, isolation monitoring is part of the IRS system and must be checked by an integrated safety controller.
It is possible to integrate a safety controller depending on customers requirements. This is usually applied, when HV supply is integrated into the emulator cabinet. There are different options for safety controllers:
PILZ PNOZ Multi II
Siemens ET200 safety modules with external CPU
Wieland safety controller.
…
Different options may be individually discussed and integrated. Examples can be found in the following pictures:
If any of the safety events occurs, the HV supply is immediately shut down safely and the “Reset” button on the left side will flash in blue color. A single event is stored until the user acknowledges this event by pressing the “Reset button”. The system will remain in safe state until the “Reset” button is pressed by the user.
When the safety event is not present anymore the HV supply is enabled again after acknowledging by the “Reset”-Button.
On the indicators on the safety controller the user may read the current status of the safety controller, while the inputs mean the following:
A signal lamp may be mounted on the emulator cabinet to indicate the following situations:
Green: no failure, no HV voltage -> it is safe to handle DUT
Red: no failure, HV voltage > 20V -> do NOT touch DUT
Orange: failure (e.g. emergency stop, isolation failure, door open, …)
An overall safety controller may be used to lock doors in case of applied voltage. These functionality may be integrated by IRS, if required.
Integrated ET200
With ET200, an external Siemens PLC CPU must be used to implement the safety program. IRS provides an example code that can be used for integration in the PLC CPU.
Integrated HV supply
Please note that with this version the integrator of the PLC software is responsible for the safety of the system. I.e. safe shutdown in any error situation must be handled by the integrator.
Check the delivery immediately on receipt for completeness and transport damage. Check the shock and tilt indicators placed on the wooden transport box.
Proceed with visible damage as follows:
Do not receive the delivery or only conditionally receive the delivery.
Make a note of extent of damage on the transport documents or the bill of delivery.
Submit a complaint.
Transport and initial commissioning implemented by manufacturer.
The packaging is to protect the individual components to the assembly from shipping damage, corrosion and other damage. Therefore, do not destroy the packaging and remove just before the installation.
Store the unit under the following conditions:
Do not store outdoor.
Keep dry and dust free.
Do not expose to aggressive media.
Protect from direct sunlight.
Avoid mechanical shocks.
The connector is rated for Thus, use power supply below this rating.
EME Control board
192.168.222.5
This device contains the main EME embedded software
EME Switch & Cool
192.168.222.11
Controller for DC- and discharge-relay, fan, and cooling pump control
EME control board
PT100
Power stage heat sink
50
IGBT_U
IGBT Phase U (close to heat sink)
65
IGBT_V
IGBT Phase V (close to heat sink)
65
IGBT_W
IGBT Phase W (close to heat sink)
65
Choke_U
Coupling inductance Phase U
80
Choke_V
Coupling inductance Phase V
80
Choke_W
Coupling inductance Phase W
80
Exciter
Optional Exciter resistor for SSM
70
H2O_In
Cooling water inlet
40
H2O_Out
Cooling water outlet
60
Switch & cool
T VARIS 1
Power stage heat sink as reference for cooling controller
50
T_VARIS 2 /
T_Exciter
In case of existing exciter -> exciter resistor, alternatively second T_VARIS
In case of following status
EME-Door open
OFF
OFF
EME Discharge Overtemperature
OFF
OFF
EME Internal Discharge active
(indicated by “Discharge feedback” signal)
OFF
ON or OFF
Discharge already activated by EME
External Discharge Control active
OFF
ON (no discharge)
HV-Voltage >20V applied
ON
ON (no discharge)
Isolation failure (independent monitoring, not integrated in EME)
OFF
OFF
WARNING!
For functional safety this chapter MUST be consequently observed!
EME is used for applications with voltages above 60V which are hazardous for life. Since the DC supply voltage is usually isolated against potential earth, an isolation monitor MUST be applied to shut down the DC voltage source in case of high or low impedance earth connection.
The user MUST ensure that live components may not be touched. I.e. leave all doors closed during operation.
Some doors include a door contact which needs to be evaluated by a safety controller which immediately shuts down the HV supply in case any of the door contacts is opened.
Furthermore, overtemperature switches must be monitored by safety controller.
Finally EME contains a discharge circuit which must be activated and de-activated externally
ATTENTION!
Damage due to improper transportation!
Significant amount of damage can occur on improper transport.
Therefore:
Use caution when unloading equipment in the delivery and the in-house transport and note the symbols and instructions on the packaging.
Remove the packaging only shortly before the installation.
ATTENTION!
Environmental damage caused by improper disposal!
Packaging materials are valuable raw materials and can be used in many cases well.
Therefore:
ensure the environmentally sound disposal
Consider the local applicable disposal regulations. If necessary, contact an authorized dealer for the disposal.
40...1000
40...1000
40...1000
Phase current continuous [A]
@ 450V @ 8kHz PWM
400
600
600
Phase current 5 seconds [A]
@ 450V @ 8kHz PWM
600
650
650
Phase current continuous [A]
@ 850V @ 8kHz PWM
200
400
600
PWM frequency [kHz]
4…12
4…12
4…12